1. What are the three main area to be verified on a new installation?
These would be equipment and material complies with relevant British Standard - all parts are correctly selected and erected - no parts are visibily damaged or defective
2. Ignoring compliance with BS 7671, earthing arrangement and load capacity what else must the designer must ensure when the work is not a new installation?
3. Give three locations that could have to comply to other statutory regulations other than the EAWR.
Approved Document Part P is a statutory document and thus dwellings
Locations that have explosive atmospheres other than Mines and Quarries
Cinemas
4. Give an example of each of the following
Limitation of discharge of energy Electric fence used on farms
Placing out of reach Pickups on electric cranes or overhead wires
Undervoltage Protective Devices Motor controllers
5. (i) What statutory document places a duty on person carrying out inspection and testing Electricity At Work Regulations 1989.
(ii) Which two groups of people does the the inspector have a duty to ensure safety of? Although worded confusingly I think himself and others.
6. What instrument should be used to carry out a continuity test of a circuit protective conductor? Low resistance ohmmeter typically with a digital instrument having a 0.01 ohm resolution
What would be unit of measurement of the above instrument? Ohms
Why would the above instrument and scale be selected? The instrument would be need to be able to measure the low resistance encountered with this kind of test
7. On a TT system which would be the first three live tests to be carried out?
Earth Electrode Resistance
Earth fault loop impedance Ze
Prospective fault current
8. Give correct names for three protective conductors that maybe connected to the MET
Main earthing conductor
Main equipotential bonding conductors
Circuit Protective Conductors
9. A cable have a resistance of 0.183 ohms is 25m in length. What be the resistance if
you had 50m of the same cable 0.366
25m in length but twice the csa 0.0915
25m in length but with half the csa 0.366
10. What are the three reasons for carrying out the ring final circuit test
Continuity of the phase, neutral, protective conductor around the ring. That no interconnections exist. Correct wiring of the ring.
11. Assuming a circuit is safely isolated give three checks to be made prior to carrying out an insulation test.
12. Excluding saunas, bathrooms, and swimming pools, name three other special locations
Construction sites.
Caravan Parks
Agricultral and horticultral sites
13. International Protection rating consists of two numbers, what do the numbers represent
The first letter
The second letter
If an X replaces a number, what would that mean
The first letter signifys protection against ingress of solids eg IP4X 1mm
The second letter signifys protection against ingree of liquids.
Where the X replaces a number it means that the protection as not been checked or that it is irrelevant.
14. When polarity testing as part of initial inspection and testing is being carried out, what are the two stages that shold be carried out. Secondly which instrument would be used?
15. External to an electrical installation what are the component parts of the earth fault impedance for a a TT system.
Even though the question does not specifically request a drawing it does help with the explanation. At the consumer Phase conductor -Main earthing conductor -Earth electrode to General Mass of Earth. At the Distributor, General Mass of earth - Earth Electrode - Main earthing conductor - Neutral on Transformer Secondary.
16. Before an installation is powered up, Zs needs to be obtained. What test value needs to be used. What else is required to be known. Finally write out the formula
Test value is (R1+R), this is CPC + phase conductor resistance)
External earth loop impedance Ze would need to be known
Zs = Ze + (R1+R2)
17. What two methods could be used to ensure the measured value of Zs complies with BS 7671.
What is the maximum accepted value for tabulated values in BS 7671 of 0.35 and 14.1
Where the ambient temperature is known then a compensation factor can be used to determine the maximum value of Zs.
The Rule of thumb is used and is the worst case scenario and reduces values in BS7671 by 75%.
Using rule of thumb
0.35 would be 0.35 * 0.75 = 0.2625 ohms
14.1 would be 14.1 *0.75 = 10.575 ohms
18. A 30mA is required to have three instrument test applied. What are they and what currents would need to be applied.
At 50% of 30mA, 15mA the RCD should not trip
At 100% of 30mA, or 30mA the RCD whould trip in under 200mS
At 500% of 30mA or 150mA the RCD should trip in under 40mS
19. What are the two types of fault current measured at source, which needs to be recorded.
PEFC and PSCC
The largest of the two needs to be recorded
20. Why is prospective fault current important in selection of protective devices?
PFC is important since the protective device would need to be able to break the fault current under short circuit conditions
For questions 21 to 26 I am going to assume you have already have access to the exam paper.
21a Electrical Installation Certificate which would include a schedule of inspection and schedule of test results.
21b The designer
21c Usage and external influences
21d BS 7671, Guidance Note 3, GS38 are all non statutory, Electricity at work regulations is a statutory document
21e Confirm that the installation adheres to the requirements of BS 7671 and that there is no visible damage to the installation
21f Earthing Arrangement - Number and type of live conductors - Nature of Supply parameters - Supply protective device characteristics
22a Although the question is perhaps a little vague I beleive the answer is that since the buildings are attached, the new services would need to be taken to the main earthing terminal
22b
- Circuit verified dead using method outlined in GS38
- CPC disconnected at main DB and shorted to the phase conductor
- At the new DB a low resistance ohmmeter is connected to the phase and disconnected CPC.
- The value obtained is (R1+R2)
Zs= 0.1 + 0.3635 ohms
Zs = 0.4635 ohms
22d The SWA would be glanded at both ends and this would mean that the resistance of the armourings would be in parallel with the CPC resulting a lower value of Zs.
23a You would need the three drawings given in GN3 or similar to explain the three stages of the test since this is a ring final circuit.
The phase and neutral conductor loop values are 40*7.41/1000 using the equation used above, thus giving 0.2964 ohms
The CPC is 40*12.1/1000 or 0.484 ohms
So taking the three loop tests we would PR1 to PR2 (PR) and NR1 to NR2 (NR) as 0.2964 and CPCR1 to CPCR2 (CPCR) being 0.484 ohms
Stage two requires that PR1 is connected to NR2 and PR2 is connected to NR1.
At each socket the value expected is (PR + NR)/4
(0.2964+0.2964)/4 = 0.1482 ohms
Stage three consists of PR1 being connected to CPC2 and PR2 being connected to CPC1
At each socket the value expected this time is (PR + CPCR)/4
(0.2964+0.484)/4 = 0.1951 ohms.
24a Precautions could be removing loads from the circuits such as lamps, being aware that the test voltage could cause damage to some electronic equipment and taking action like linking the phase and neutral conductors together.
24b Factors are the conditions of the individual circuits being tested, since the circuits are in parallel the value of the test will be less than that of the lowest test that would be obtained on individual circuits.
24c The test voltage needs to be 500 Volts. A test result lower than 2 Megohms would require further investigation although the minimum accepted result is 0.5 Megohms.
24d 1/Rt = 1/R1 +1/R2 etc
Since there are 14 circuits with values of minimum 200 Megohms. 1/Rt = 14/200 therfore
Rt = 200/14 Mohms.
= 14.2857 Mohms.
25a and b Circuit 10 is 80 metres using 1.5 mm T&E so CPC will have a csa of 1 mm. The maximum Zs is 4.8 ohms.
The Phase conductor (R1) resistance will be 80*12.1/1000 = 0.968 ohms using values in figure 2.
The Neutral conductor (R2) resistance will be 80*18.1/1000 = 1.448 ohms
Zs = Zdb + (R1+R2) where Zdb is earth loop impedance of new distribution board which from question 22 is 0.4635 ohms .
Zs = 0.4635 + (0.968+1.448)
Zs = 2.8795 ohms
Using the 3/4 rule of thumb maximun Zs value becomes 4.8 *3 /4 = 3.6 ohms
The value of Zs would be acceptable.
(Hard to believe that only 6 marks have been awarded for all that work and why did it require reference to a previous result)
25c A drawing here will assist to explain the procedure
At the furthest point of the circuit with all switches closed connect the earth loop impedance tester to the CPC and then the connect the other lead to the phase conductor, remembering that this is a live test and the risk needs to assessed. The result obtained will be Zs for the circuit. If the circuit was a two or more way arrangement, each way would need to be tested and the highest value would be recorded as the Zs.
26a. The basic drawing can be found in the On-Site Guide. TN-C-S would mean that the neutral and earth would be seperated in the distributors metering at the consumers end. The circuit would also include the main protection device, the protection device for the new DB and also the 20A MCB feeding the air curtain (Just what is an air curtain, not exactly common and therefore likely to create a problem to those taking the exam, IMHO).
26b. PEFC is given by Uo/Ze for the source thus PEFC = 230/.1 = 2.3kA
26c. Since Zdb is higher than Ze it can be assumed that the PEFC will be less than at the source.
26d. For this question we could say refer to question 20 since for me the answer is the same. This time the mark is not 1 but 2 however.
The PFC is important in selection of protective devices since this is the current that the device will need to break in case of a fault of negligible resistance.
These are the answers I have since worked out or found since taking the exam and although many seem to be similar I cannot be certain
I you disagree with the answers please add a comment